The DTEC Ltd. GESADC termination board connects via ribbon cable to the Gespac analog input card. This Gespac analog input card and GESADC termination board allows connection and protection for 16 analog inputs. The connection to peripheral equipment is provided by the screw type terminal strips and the protection is provided by 15 VDC avalanche zener diodes. The Gespac analog input is setup to accept an analog range of +15 to -15 VDC. The GESADC termination board receives its' ground from the Gespac Card through the ribbon cable, therefore failure to connect the GESADC termination board properly to the Gespac card will result in no or improper operation of the termination board.

 

Stock Item. US$145.00

 

Download

Circuit Description:

The input channels of the Gespac analog input card can receive a voltage range of -15 Vdc to +15 Vdc. The zener diodes protect the input circuitry by shunting current when the input voltage is over 15.6 Vdc or under -15.6 Vdc. The zeners are rated for 500 mWatt each. For download of Schematic and General Arrangement in DXF format goto download files.

 

Connector P1 Screw Type Term Block

Description

Connector P2 Ribbon Cable Connector

1

Channel A0 input

31

2

Channel A1 input

27

3

Channel A2 input

23

4

Channel A3 input

19

5

Channel A4 input

15

6

Channel A5 input

11

7

Channel A6 input

7

8

Channel A7 input

3

9

Digital Ground

1

10

Channel B0 input

32

11

Channel B1 input

28

12

Channel B2 input

24

13

Channel B3 input

20

14

Channel B4 input

16

15

Channel B5 input

12

16

Channel B6 input

8

17

Channel B7 input

4

18

Analog Ground

30,26

19

Analog Ground

22, 18

20

Analog Ground

14, 10

21

Analog Ground

6

22

Analog Ground

2

23

Digital Ground

34

24

External Trigger

33

25

Not Connected

 

26

Not Connected