DTEC Ltd.
GFMIV
Ground Fault Monitoring
And Interruption System
CONTENTS
1.0 Ground Fault Monitor
and Interruption Manual............ 3
1.1
Introduction:.............................................................................................. 3
1.2
Specifications:.......................................................................................... 3
2.0
Installing GFMIV........................................................... 4
2.1
General Information................................................................................. 4
2.2
Rear Panel Connections:....................................................................... 4
2.2.1
Relay Common and Normally Closed Terminals:................ 4
2.2.2
Sense Circuit Terminals:........................................................... 4
2.2.3
Chassis Reference:.................................................................... 5
2.2.4
Power Cord Connection:........................................................... 5
2.3
General Operation and Front Panel Description:............................. 5
2.3.1
Power Switch and Light............................................................. 5
2.3.2
Reset Button:............................................................................... 5
2.3.3
Channel Indication Lights:........................................................ 6
2.3.4
Channel Select Rotary Switch:................................................ 6
2.3.5
Panel Meter:................................................................................. 6
2.4
Sense Blocks:........................................................................................... 6
3.0
Panel Drawings............................................................. 7
Fig.
1. Rear Panel Connections................................................................... 7
Fig.
2. Front Panel.......................................................................................... 7
Appendix
A Circuit Drawings............................................. 7
Fig.
3. Sense Block Wiring........................................................................... 8
Fig.
4. System Block Diagram..................................................................... 9
Fig.
5. Ground Fault Monitor Wiring Diagram......................................... 10
Drawing
Following Page:.............................................................................
Fig.
6. Ground Fault Relay Board Schematic......................................... 11
Fig.
7. Ground Fault Monitoring Board GA.............................................. 12
Fig.
8. Ground Fault Monitoring Board
Schamatic................................ 13
Fig.
9. Ground Fault Monitoring Termination
Board Schematic........ 14
Appendix
B GFMIV Setup Procedures............................... 15
Appendix
C Trouble-Shooting............................................ 18
Power
Failure................................................................................................... 18
Incorrect
LED Operation............................................................................... 18
Incorrect
Analog Meter Operation.............................................................. 19
Override
Condition......................................................................................... 19
Appendix
C Optional DC Relay Outputs............................. 20
This document
contains setup, wiring diagrams and an
overview of the operation for the GFMIV Ground Fault Monitoring and
Interruption System. The ground fault
system is intended to protect equipment and people from failure or injury. The system measures and indicates the amount
of "leakage" résistance to the reference chassis ground. The system also provides the interruption of
a faulty circuit by means of interrupting a path to a contactor or switching
device.
Mechanical:
Dimensions: 19"
wide x 5.22" height x 18" deep.
Weight:
Electrical:
Power input: 120
Vac @ 60 Hz @ 1amps
Fuse: 250 Vac @ 3amps AGC
Number
of circuits: 8 individual sense
circuits/8 individual relay contacts
Monitored
circuits: 5 to 1000 Vdc and/or 24 to
3000 Vac 1 or 3 phase @ 60 Hz
(Higher
voltages available)
Interruption
point: Factory set 500 Kohms
Output
Relay: 240 Vac @ 10 amps Note:
(optional
switching to 480VAC @ 25Amps)
Optional
Installation of
the ground fault monitoring system requires the connection of the power cord,
chassis reference, relay output circuits and sense inputs to the correct sense
blocks. These sense blocks are different
for Single phase/DC circuits and 3 phase circuits. The sense blocks are installed between the
monitored circuit and the sense inputs.
The typical connections for these blocks are in Appendix A. The relay outputs are triac switches that
open upon a ground fault condition.
Typical installation is to connect the coil of a contactor through this
relay and hence be interrupted and disconnected if a ground fault condition
arises.
The
rear panel has connections for 8 - Relay Common Terminals, 8 - Relay Normally
Closed Terminals, 8 - Sense Circuit Terminals,
2 - Chassis Reference Terminals and a 120 Vac power cord. The block diagram and examples for the rear
panel wiring is located in Appendix A. There can also be connections fro the
Optional DC Relay contacts.
The ground fault
system can monitor up to 8 independent
AC and/or DC circuits. Each
circuit has a solid state relay with a triac output that can interrupt the
corresponding channel if a ground fault condition appears. Typically the Relay Common will connect to a
power source (line) that enables a contactor or switching device. The Normally Closed will connect to one side
of the coil or switching device. If no
ground fault condition is present the path will be completed by the solid state
relay closing. If a ground fault
condition is present the path will be interrupted by the solid state relay
opening. See wiring example in the
drawing appendix A. The solid state relays can only switch off AC circuits.
The sense circuit
inputs should be connected directly to the sense blocks via a 22 to 20 gauge
wire. The sense blocks are then
connected to the monitored circuit. See
appendix A for connection to circuits.
Using Twisted pair wire shielded to chassis ground will reduce the
chances of an erroneous GFI trip.
The chassis
reference input is essential for proper operation of the ground fault system
and must be connected to the system chassis ground or chassis ground to be
referenced. Typically this is the
chassis ground of the hull, umbilical, rack etc. The 2 terminals are tied together inside the
unit so connection of either terminal will be correct. If this terminal is not connected to chassis
ground the ground fault system will not function correctly.
This terminal is not internally tied to the chassis ground connection on
the power cord even though most likely these are the same. This is done to allow the user to choose the
least electrically noisy contact to use for the chassis ground connection.
The power plug
connection is a standard power supply cord set.
The input power of 120 Vac 60 Hz @ 1 amps must be stable and protected
if possible for proper use. The power
cord connector contains an integrated pull-out fuse holder with fuse and a
spare fuse. This fuse rated for 3 Amps
and is the only fused associated with the system.
The operation of
this ground fault system is to display and interrupt an electrical circuit if
there is a resistance of 500 Kohms between a conductor and chassis ground. The channel with the ground fault will
illuminate a Light on the front panel, and, with that channel selected by the
rotary switch the resistance will be indicated on the panel meter. The meter can only indicate one channel at a
time. Use the selector to choose the
channel to have displayed by the panel meter.
The front panel contains the power switch and light, reset
button, channel indication lights, rotary switch for analog channel select, and
analog panel meter.
The power switch
and light indicate whether the unit has power to it. It is critical that the 120 Vac be stable and
constant as fluctuations in this level could cause the unit produce incorrect
readings. If the light does not
illuminate after throwing the switch check to ensure that the power cord is
plugged in and the fuse is not blown or incorrectly installed.
The reset button
function is to reset the solid state relay board to the normally closed
position after it has been interrupted.
If the ground fault that caused the interrupt has been repaired or
corrected the reset button is depressed to resume proper operation. While the reset button is being depressed it
is possible to "override" the relay output and force it closed. Operators must be aware of this state as you
could override a interrupted circuit which still has a Ground Fault Condition.
An illuminated
red light indicates that the ground fault level of that channel has reached 500
Kohms or below and the circuit has been interrupted. The channel will stay interrupted until the
reset button is depressed and the light goes off. If the light does not go off after the reset
button has been depressed then the channel still has a ground fault present and
should be checked more thoroughly.
The rotary switch
selects which analog value is displayed on the analog panel meter. The switch can be rotated to any of the 8
sensed circuits and the corresponding resistance value of that circuit will be
displayed on the panel meter.
The panel meter
displays the resistance value of the circuit selected.
A sense block is
required for each channel to be monitored and sense blocks may vary from
circuit to circuit due to the type of circuit to be monitored. It is essential that the proper sense blocks
are used in each circuit or incorrect and faulty readings could result. The input resistance the sense circuit
requires for proper measurements is 600 Kohm, therefore; in a DC or 1 phase AC
circuit the 2 resistors must be 1M2. In a 3 phase AC circuit the 3 resistors
must be 1M8. For monitored circuits up
to 1000 volts use 1/2 watt resistors, for monitored circuits up to 2000 volts
use 1/2 watt resistors and for monitored circuits up to 3000 volts use 1 watt
resistors. Try to keep the sense blocks
close to the high voltage and use 22 to 16 gauge wire for the sense wire to the
GFM unit. This keeps the high voltage
within the designated area. For
connection examples see appendix A. The
resistors must be appropriately voltage sized.
Circuit
description:
The DTEC Ltd.
GFMIV ground fault monitoring board places a high impedance (~3M ohms) voltage
source of +25.6 VDC, with respect to chassis ground, onto eight circuits. It then measures the drop across sensing
resistors. These resistors are a combination
of 2 or 3 resistors making 600K Ohms. If
the circuit being monitored is 3 phase the resistors are 1M8. If the circuit being monitored is single
phase or DC the 2 resistors are 1M2. If
a ground fault condition is developing this +25.6 vdc level decreases. If +25.6 VDC is present (with respect to
chassis ground) on the monitored channel there is no ground fault. As the resistance from the circuit to chassis
ground decreases this voltage drops, this produces an increasing analog output
voltage for that channel and in the event the resistance drops below 500K Ohms
the digital output for that channel goes active.
There are 5 sections to the circuit board:
Power
Supply - The 2 - DC-DC converters receive a logic +15 vdc and output +/- 15
vdc. These work in series to create a
+60 vdc circuit and a single +15 vdc with respect to chassis ground.
Voltage
Comparitor - This section compares the trip level (set by Pot 11 and measured
on test point 1) to the measured sense input level. A Voltage of 6.00VDC at test point 1
corresponds to a ground fault resistance of 500K Ohms.
Digital
Output - This section triggers the digital output to be enabled. This level is either active high (+5 or +15c
vdc) or active low (0 vdc). The active
high/low is selectable by Jumper 1
(JP1). No matter what the state of JP1
the LEDs on the board will only illuminate if the ground fault trip level is
reached. JP1 only affects the outputs
connections to the board.
Analog
Amplifier/Isolator - This section outputs a single analog value which is
connected to one of the eight channels as selected by the bit selects. ( C12,
C14, and A14). The analog is isolated
from chassis ground (analog output referenced to power supply ground). The analog voltage should range from +0.00 to
+5.00 vdc. 0.00VDC is a high resistance
from the selected channel to chassis ground (normal condition), 5.00VDC is a short from the selected channel
to chassis ground.
Bit
Select Input - This is the section which selects the channel that will be
routed through the analog isolator and is sent to either the Ground Fault Meter
(
Bit
Select Input Terminal Level
Monitored C12 (lsb) C14 A14 (msb) Edge Connector
2 3 4 Termination
Card
1 1 1 1
2 0 1 1
3 1 0 1
4 0 0 1
5 1 1 0
6 0 1 0
7 1 0 0
8 0 0 0
**note**
lsb - Least Significant Bit
msb -
Most Significant Bit
0 -
Logic Ground
1 -
Logic +15 vdc
Board Setup
The ground fault
board is set up at the factory to measure ground faults ranging from
No in circuit wiring should be connected to the sense lines
only the test wiring.
Connections for the board:
Edge Termination Board Description
Connector Connection
C2 39 Chassis Ground
C4 38 Logic Ground
C10 1 Logic +15 vdc
C12 2 Bit Select 1
(lsb)
C14 3 Bit Select 2
A14 4 Bit Select 3
(msb)
C16 5 Digital Output
Alarm For Channel 1
C18 6 Digital Output
Alarm For Channel 2
C20 7 Digital Output
Alarm For Channel 3
C22 8 Digital Output
Alarm For Channel 4
A16 9 Digital Output
Alarm For Channel 5
A18 10 Digital Output
Alarm For Channel 6
A20 11 Digital Output
Alarm For Channel 7
A22 12 Digital Output
Alarm For Channel 8
C24 37 Analog Output
C26 13 Channel 1 Input
Sense Line With External Resistors
C28 14 Channel 2 Input
Sense Line With External Resistors
C30 15 Channel 3 Input
Sense Line With External Resistors
C32 16 Channel 4 Input
Sense Line With External Resistors
A26 17 Channel 5 Input
Sense Line With External Resistors
A28 18 Channel 6 Input
Sense Line With External Resistors
A30 19 Channel 7 Input
Sense Line With External Resistors
A32 20 Channel 8 Input Sense
Line With External Resistors
** Note you must use external sense resistors when using
inputs 13 to 20
Test points used on the board:
-
Input logic voltage level point and ground point found in the rear left corner.
-
Chassis ground point found near LED 8
-
TP1 found near power LED9 and C18
-
TP3 found near C19 and P10
Setup
Tune Pot 11 (P11) so the voltage
at Test Point 1 (TP1) is +6.00 vdc with respect to chassis ground. This calibrates the digital output trip level
to activate at ~500K ohms.
Tune Pots 1 through 8
(P1 to P8) so the voltage at the junction of the diode and capacitor is
+10.00 vdc with respect to chassis ground.
For example to set up channel 1:
- place the "+" ve probe of multi-meter on the
junction of D1 (diode 1) and C1 (capacitor 1) and the "-" ve on the
chassis ground.
- tune P1 until the multi-meter reads +10.00 vdc this
happens near the very end of the pot.
Eg. To setup channel 4:
- place the "+" ve probe of multi-meter on the
junction of D4 (diode 4) and C4 (capacitor 4) and the "-" ve on the
chassis ground.
- tune P4 until the multi-meter reads +10.00 vdc this
happens near the very end of the pot.
Tune Pot 9 (P9) so with a 5M0 ground fault (with the sense
resistors in the circuit) the analog output value is +0.620 vdc with respect to
logic ground.
This
only needs to be done once because its the same for all channels.
Eg. -
place a wire on terminal 13
-
place a 5M0 ohm resistor between chassis ground 39 and channel 1 input sense lines 35 or 36 ( they should be tied
together).
- place the "+" ve
probe of the multi-meter on the analog output 37.
-
place the "-" ve probe on the logic ground point or 38.
-
tune P9 until the meter reads +0.620 vdc
Tune Pot 10 (P10) so with a 0 ohm (short to chassis ground
with the sense resistor in the circuit) the analog output reads +5.00 vdc.
Eg. - place a wire on terminal 13
-
place a wire between chassis ground 39 and channel 1 input sense line 13
- place the "+" ve probe
of the multi-meter on the analog output 37.
-
place the "-" ve probe on the logic ground point or 38.
-
tune P9 until the meter reads +5.00 vdc
Selectable features:
Jumper 1 JP1 -
This selects the digital output from either active high or active low level.
Jumper installed is active low. Jumper removed is active high.
+5 vdc or +12 vdc
- This is a hard wire jumper - JP3
- found in front of P11. If the jumper is between the center and left
points the digital output level is +5 vdc.
If the wire jumper is between the center
and the right points the digital output is +12
vdc.
check power cord into the unit and
into the wall.
check fuse in power cord connector
in back of unit.
check wall breaker.
check
power switch and light for proper operation.
check
to ensure that internal power supply is set to 15 Vdc
check to ensure that the chassis
reference terminal on the back panel is connected to the chassis ground.
check to ensure that the sense
blocks are connected properly and the correct sense block is being used for
each monitored circuit.
check
all connections for the LEDs using the GFM schematic.
check that the power supply is set
to 15 Vdc.
check to ensure that the sense
blocks are connected properly and the correct sense block is being used for
each monitored circuit.
check that the channel select
switch is working properly.
check the diodes that are used to
the generates the 3 bits for the channel select for the ground fault board.
check
all connections to the analog meter using the GFIWIRE schematic.
an override condition can be
caused by depressing and maintaining the reset switch. This is not recommended as serious harm may
result to equipment and/or humans.
Please call DTEC for support if the above information
doesn't correct the problem.
Optionally
there are DC solid state relays which are installed to compliment the normally
installed normally closed 25-240VAC relays.
These relays (both the optional DC and usual AC) are used to interrupt
the current through of the users power control contactors upon detection of a
ground fault.
Nominally the users equipment is
controlled by AC driven contactor coils.
In the event that the user has DC coils and DC control system the
optional solid state relays must be used to interrupt these circuits. The DC relays are good to 100VDC at
1Amp. See the GFM wiring diagram for
detailed hook up.